Koldlok Surface Mount - Model #2020, #2030, #2040

Shop Now
Data Clean Surface Mount

Applications

Installation in active raised floor data centers to seal cable openings without affecting operations.

Features

KoldLok is a permanent airflow sealing solution which will accept perpetual cabling1 changes without requiring technician training, policing, or labor to cut, scribe, re-install, reposition, or modify any part of the grommet.

KoldLok is the best2 low cost solution for achieving the hardware air intake temperature and humidity conditions required for maximum reliability and performance by computer and communication manufacturers.

The KoldLok system of overlapping, offset, multi-layer, interwoven bypass airflow closures utilizing KoldFilaments™ guarantees sealing effectiveness. (U.S. Patent No. 6,632,999.)

KoldLok avoids unnecessary investments in additional cooling capacity* by reducing bypass
airflow which increases both the effectiveness and usable capacity of existing cooling equipment.

KoldLok's 33 square inch usable cable area is sufficient to accommodate virtually all cabling
requirements (typical cable fill area is less than 5 square inches, after plug has passed through).

KoldLok's unique separating sections allow for installation during equipment operation resulting in absolutely no downtime.

1 It is estimated that, on average, 25% of all raised floor openings are re-cabled quarterly.

2 Filaments are premium grade Nylon 6. Filaments made of styrene, ABS or polypropolene fall below KoldLok product standards.

*For a typical 10,000ft2 computer room with 170 cable openings, preventing the 49,000 cubic feet per minute bypass airflow loss through unsealed cable cutouts is equivalent to recovering the output from five or more 20-Ton cooling units.

Specifications

Grommet is inherently self-sealing using a multi-layer, overlapping, and interwoven, bypass airflow closure system consisting of:
  • Two opposing overlapping arrays of 0.010" diameter upper filaments
  • Two opposing arrays of 0.020" diameter lower filaments
  • 3,100 filaments per cross sectional inch

Grommet filaments are premium grade Nylon 6 ensuring bristle flexibility, compliance, and selfsealing recovery. Filaments are conductive with static dissipation properties.

Grommet and filaments safely bleed off any static build up on cables passing through the cable opening caused by high velocity airflow (triboelectric effect). Grommet is an integral part of the raised floor¹s static dissipation system providing 1 GigaOhm of resistance.

Grommet shall achieve 100% bypass airflow sealing in areas undisturbed by cable penetrations at static pressures up to 0.10 inches of water column. When penetrated by four 1/2" cables, sealing is 100% effective at the static pressure required to cool up to 3 kW/cabinet with a 96% sealing effectiveness at a static pressure of 0.10".


Grommet ships with custom adhesive mounting kit consisting of:

  • One edge-mount cellular urethane foam strip
  • Two 3M™ 4300 series single-coated, single-sided, pressure-sensitive acrylic adhesive foam mounting tapes
  • Three 3M™ 4300 series single-coated, double-sided pressure-sensitive acrylic adhesive foam mounting tapes
  • Eight 2.5mm Youngboard-C, conductive grade, cross linked polyethylene foam buttons for ESD dissapation

Grommet utilizes an engineered separating mechanism using high-grade polymer joiner bars which lock into position. The Grommet can be perpetually separated to facilitate recabling.

Grommet is a heavy duty, molded, high impact resistant polypropylene housing with a wide trim lip to provide a bumper to inhibit equipment casters from falling through raised floor openings and to allow imprecise tile cutting.

Grommet metal components are anodized to resist corrosion caused by high humidity and are assembled with positive fasteners that will not pull through the plastic.

*Ensures easy passage of cable heads and power connectors including a 100 amp Hubbell™ power plug (or equivalent 4.125" x 4.125" connector).

 

Model #2020
Model #2020

Model #2030
Model #2030

Model #2040

Model #2040

Overall Size

11" x 8 1/4" x 1 1/8"

12" x 11 3/4" x 1 5/16"

12" x 15" x 1 5/16"

Grommet Usable Cable Opening Size*

8 1/4" x 4"

8 1/4" x 4"

8 1/4" x 4"

Grommet Total Cable Opening Size

8 1/4" x 5"

8 1/4" x 5"

8 1/4" x 5"

Maximum Cutout
Size Sealed

10 " x 7 1/4"

10" x 9 3/4"

10" x 13"

  Buy Now Buy Now Buy Now

Background

ELIMINATE BYPASS AIRFLOW
Unsealed cable openings allow 63% or more of bypass air losses in a typical computer room. Excessive bypass airflow will reduce underfloor static pressure to as low as 0.01" of water column. This is much lower than the 0.025" required for cooling high heat densities (> 1 kW/rack or cabinet). Unmanaged bypass air results in vertical and zone hot spots and introduces significant cooling inefficiencies.


A CLEAR SOLUTION
The KoldLok Surface Mount Raised-Floor Grommet automatically reseals raised-floor openings, permanently solving bypass airflow problems.

Tools Needed:

  • Cutting tool (per floor tile manufacturer recommendations)
  • Tape measure
  • Isopropyl alcohol or equivalent for cleaning

Preparation:

Cutting Raised Floor Tiles
Each raised floor tile manufacturer provides instructions to properly and safely modify their products. Installers must be familiar with and observe tile manufacturer’s recommendations with regard to applicable tools, cutting procedures, the design load capacity of the cut tile, and any additional underfloor supports requirements for cut raised floor tiles.

*IMPORTANT: Data center best practices indicate that tiles should not be cut within the raised floor environment in order to protect equipment from harmful particulates. However, quick clean up of any debris or loose particulates is always recommended.

Clean the tile and bottom surface of the grommet using an alcohol wipe or a clean cotton cloth, damp with a solution of at least 50 percent isopropyl alcohol.

HELPFUL TIP: When choosing your cleaning cloth, do not use fabric or paper that will disintegrate or leave particles that could interfere with the adhesive or contribute to airborne contamination.

General Information

Dimensions and Tile Cutting Requirements Inches (W x D x H) Millimeters (W x D x H)
Part No. 2020 Original - Overall size 11” x 8 1/4” x 1 1⁄8” 279 x 210 x 29mm
Product height above the raised floor 1 1⁄4” with mounting system installed 32mm
Maximum cutout size sealed 10” x 7 1/4” 254 x 184mm
Usable cable area 33 sq in 21336 sq mm
Part No. 2030 Large - Overall size 12” x 11 3/4” x 1 5⁄16” 305 x 298 x 33mm
Product height above the raised floor 1 7⁄16” with mounting system installed 37mm
Maximum cutout size sealed 10” x 9 3/4” 254 x 248mm
Usable cable area 33 sq in 21336 sq mm
Part No. 2040 XLarge - Overall size 12” x 15” x 1 5⁄16” 305 x 381 x 33mm
Product height above the raised floor 1 7⁄16” with mounting system installed 37mm
Maximum cutout size sealed 10” x 13” 254 x 330mm
Usable cable area 33 sq in 21336 sq mm

SAFETY REQUIREMENTS

Installers must be familiar with standard safety and risk management practices when working in raised-floor environments and when modifying floor tiles.

Effective Installation of Cables

In order to minimize any air loss from the rack hole selection, make sure to allow for adequate slack in the cables. If the cables are under too much tension, the grommet may be pulled apart, resulting in a gap that will cause an increase in the flow of air escaping through the rack.

Maintaining Proper Cooling of Equipment

Failure to follow computer manufacturer’s guidelines for maintaining proper cooling may result in the overheating of equipment. Before sealing cable cutouts, ensure that there is adequate airflow to the intake sides of computer equipment or cabinets through devices such as perforated floor tiles or grates. Achieving proper airflow to the intake side of the computer equipment and/or cabinets is the responsibility of the customer.